The Omniguard model 660 is available in two versions, one for standard industrial applications where a maximum operating temperature of 85°C is the norm, and a second which is capable of operating at a maximum sustained temperature of 125°C. This version is especially well suited for turbine enclosure and high temperature industrial applications. Both versions are available with an automatic self-test function to monitor the detector’s ability to sense fires and report a fault condition when impaired.
Key Features:
- Available in special high temperature version (-40°C to +125°C)
- All inclusive three-year warranty on parts and labor
- Widest field of view in the industry (120°)
- Robust, weatherproof enclosure for indoor or outdoor applications
- FM, CSA, IECEx and ATEX approved
- Improved, advanced through-the-lens diagnostic self-test
- Long range detection
- Self-contained, explosion-proof enclosure
- Economical no-test version available
- Field configurable relays and sensitivity
- State-of-the-art microprocessor control
- High intensity, localized indication of fire or fault
Performance Ratings
Responsive to hydrocarbon (gasoline, propane, methane, alcohol, etc) and non-hydrocarbon
(hydrogen, silane, hydrazine, magnesium, etc) flames.
Third-party performance certified to detect saturating signal source in 15 milliseconds,
1 square foot gasoline flame at 50 feet in 1 second. Horizontal performance envelope of 120°.
Environmental Ratings
Rated:
- Class I, Division 1, Groups B, C &D (explosion proof)
- Class II, Division 1, Groups E, F & G (dust ignition proof)
- NEMA 4X weatherproof, dust-tight, watertight
- CE0081 II 2 G/D
- Ex d IIB + H2 T5 Gb for gas on 660-0XXXX
- Ex tb IIIC T100°C Db IP6X for dust on 660-0XXXX
- Ex d IIB + H2 T4 Gb for gas on 660-1XXXX
- Ex tb IIIC T135°C Db IP6X for dust on 660-1XXXX
Optional stainless steel housing available with passive finish per MIL-5-5002C, Type 1.
Standard operating temperature range: -40° to +85°C (-40° to +185°F).
Special high temperature version: -40° to +125°C (-40° to +257°F).
Spectral response
Ultraviolet peak sensitivity of 2,2 μm.
Detector inputs
Inputs
- nominal voltage: 24 VDC
- range: 20 to 30 VDC
Power consumption
- standby: 90 mA
- alarm: 110 mA
- auto and manual test: 250 mA
Detector outputs
Relay
- relays (2): fire, trouble, dry contacts, hermetically sealed
- rated: 2 A at 28 VDC. User selects NO or NC
- fire relay: user selects latching or non-latching
Current loop (standard version) 0 to 20 mA output
- 20 mA = fire
- 4 mA = ready
- 0 mA = 20
Programmable RS-485 serial output
Mechanical considerations
Weight: 5 lb (aluminum)
13 lb (stainless steel)
Height x width: 4.90 in x 5.50 in
Conduit entry: 3/4-14 NPTF or M20-1.5
Optional accessories
Swivel mount: No 4651027 (used with aluminum)
No 70991 (used with stainless steel)
Portable test unit: No 43808-2
If you would like to receive more information about Omniguard Model 660 UV Flame Detectors please contact Forberg Scientific.
P: 248-288-5330
F: 248-288-4204
Email: mechanicalsales@forberg.com